This video from the 2022 NCC Seminars discusses Section G Ancillary provisions from NCC 2022 Volume One.
Transcript
0:00
[Music]
0:10
Hello my name is Graham Moss, i'm the Principal Building Surveyor for the Australian Building Codes Board
0:15
this video is a brief update on NCC 2022 ancillary provisions Section G.
0:21
The first change to cover today is G1D4, what's known in 2019 as G1.3 and that's outdoor play
0:29
spaces for early childhood centers. Now it's always been the case that the outdoor play
0:33
space needs a 1926.1 compliant pool fence that is 1926.1 the reference standard for pool fencing.
0:40
So for this reason the fence which is at the edge of an outdoor play space will need to be
0:45
at least 1.2 meters tall. This year we've added (1) (b) and (c) as shown by the orange line on this slide
0:52
for where there is a fall of two meters or more, now this fall could be because of the retaining wall.
0:57
For instance or for other landscaping, however this provision was developed to cover outdoor
1:01
play spaces that are found on balconies or on rooftop spaces. So if you have a
1:06
2 meter fall the fence needs to be at least 1.8 meters tall to meet these requirements.
1:13
Next I want to cover is Part G5 construction in bushfire prone areas there's been some
1:19
significant changes this year, because under NCC 2019 in the national provisions
1:24
the only buildings that Volume One requires to meet bushfire requirements are a
1:30
Class 2 or 3 building or an associated Class 10a like a deck or a bin store.
1:36
For NCC 2022 we have a new section for the Class 9 buildings that you
1:41
see listed here they're hospitals, early childhood centers, primary and secondary
1:45
schools and residential care buildings such as aged care buildings. Now note this isn't
1:50
every type of Class 9 building for example you don't see a sports stadium listed here
1:55
these particular building types are ones where the occupants are vulnerable and
1:59
therefore it's appropriate to provide extra provisions to protect them in a bushfire event.
2:06
I'll take you to those extra provisions shortly but the first thing to note if these Deemed-to-Satisfy
2:11
provisions for these special Class 9 buildings apply only to BAL 12.5
2:17
now you're probably aware of the AS 3959 bushfire attack level the BAL rating
2:21
system, that's a risk rating system which based on the likelihood of exposure to bushfire attack.
2:27
These DtS provisions for certain Class 9 buildings run out at BAL 12.5, if you go up to
2:34
BAL 19 or above you need to do a performance solution however up to bushfire prone land up to BAL 12.5
2:41
are covered by these Deemed-to-Satisfy provisions. If you're familiar with the
2:45
current bushfire provisions for Class 2 and 3 buildings you'd be aware that for these
2:49
particular buildings we refer you to AS 3959 for construction requirements. Now for these special
2:55
Class 9 buildings it's different we don't refer to AS 3959 instead we send you to Specification 43
3:01
which contains the construction requirements for these special buildings, now these construction
3:06
requirements do exceed those that are found in AS 3959 I'll step you through those right now.
3:12
First provision to show you is clause 2 in Specification 43 separation from classified vegetation now this
3:19
is quite similar to requirements found in AS 3959 what we're requiring is a minimum
3:24
distance from vegetation that's specified and that's a concept straight from AS 3959.
3:30
Next is clause 3 separation between buildings you have three options and I'll explain those
3:35
options using the hypothetical scenario with these three buildings A, B and C the first option is a
3:42
distance of at least 12 meters between buildings as is the case between A and B here. If you have
3:48
12 meters or more then you meet the requirements but buildings B and C are within 12 meters of each
3:53
other and that's where clause 2(b) comes in there are more options inside this Clause that both
3:59
involve envelope protection so the first option is to provide frl60/60/60 walls as shown on building B.
4:07
The next option as shown on building C is a tested envelope system now that entire envelope needs to
4:15
be submitted to a test under AS 1530.8.1 for a flux of at least 10 kilowatts per square meter.
4:23
Now AS 1530.8.1 isn't a primary reference in NCC 2019 however it is caught up by AS 3959
4:31
it's the standard that's used by manufacturers and people like that to test windows, doors and
4:36
other things to find out what BAL those could withstand and of course it can be used also
4:40
for to rate a wall or a roof system as an option for buildings within 12 meters of another building.
4:47
So that's clause 2 separation between buildings we also require separation from
4:52
hazards including a boundary or an open car park that's clause 4.
4:56
clause 5 requires protection from other hazards like a bin compound now that
5:01
needs to be at least 10 meters but if you don't achieve 10 meters you can use the
5:05
same protection methods that I outlined before an frl60/60/60 wall or the tested envelope system.
5:13
So with four provisions about separation you can see that this is an important part of the
5:17
fire safety strategy for bushfire protection for these Class 9 buildings and of course that's not
5:21
new it's a established way of protecting buildings from the effects of bushfire. However that's not
5:27
all we also have clause 6 which is requiring a non-combustible path at least one and a half
5:32
meters wide around the building so you can't have garden beds for instance right up against
5:36
your building. Next is clause 7 access pathways what you'll find in this provision are additional
5:42
requirements beyond those found in D1.10 for exit pathways from buildings. Clause 9 is important to
5:49
note there needs to be internal tenability maintained for the duration of the bushfire
5:54
and so clause 9 contains special requirements in order to ensure that that internal tenability is
6:00
met. Clause 10 building envelope you have to build the walls and roof to AS 3959 as if your building
6:07
is in a BAL 19 Zone even though it's only up to 12.5 for which these provisions supply.
6:14
There's also water supply requirements even if your building doesn't need a fire hydrant
6:19
you need to at least have a water supply that could be a pool or a dam you'll find more
6:24
details in clause 11 of Spec 43. There's also a requirement for emergency power, now
6:30
this power system needs to be able to run the internal tenability systems for clause 9
6:35
and other things for a period of at least six hours. Signage is also required in clause 13
6:42
there has to be a sign somewhere saying don't store combustible material near the building.
6:47
And of course, finally vehicular access has to be provided as for a large isolated building this
6:52
requirement is to ensure that the fire brigade can easily access the building and affect operations.
6:58
Now this is a very brief overview of the new Class 9 bushfire provisions, if you are
7:02
working with Class 9 buildings in bushfire prone areas I do recommend that you have a
7:05
closer look at Part G5 and Specification 43 in the production version of NCC 2022.
7:14
Also new for Section G is livable housing or you might know of this as accessible housing
7:19
this is also in Volume Two in Part H8, what is livable housing? Well I'll explain it this
7:25
way currently there are no accessibility requirements in the NCC for the internal
7:30
parts for Class 2 unit or indeed for a Class 1a house to be accessible, there's no requirement
7:35
under NCC 2019 for these internal dwellings to be accessible but that changes with NCC 2022.
7:42
Both Volume One and Volume Two refer to a new ABCB reference standard the Livable Housing
7:47
Design Standard I've talked about making these dwellings accessible but livable
7:52
housing isn't so much about making these accessible but rather making them adaptable.
7:58
This is a diagram from the standard and under the standard you need to have a toilet on the entrance
8:02
level of the dwelling that toilet has to be next to a wall and though the grab rail doesn't have
8:07
to be installed for the final inspection you do need to have blocking or sheeting installed so as
8:11
to be able to receive a handrail in the future. So the handrail doesn't have to be there for
8:16
the final inspection but the blocking or the sheeting needs to be there. So of course this
8:21
is a way amongst others of how the Livable Housing Standard makes a dwelling adaptable.
8:28
There are other requirements listed on this slide we're talking about step-free entry, circulation
8:32
requirements as shown by this diagram here, corridor widths of one meter or more
8:39
minimum doorway widths, also the requirement for a step-free shower. Now at the time of recording
8:44
of this video the technical requirements of the Livable Housing Standard had not been
8:48
finalized so of course we're not in position to update you fully during this video, however
8:54
do watch our website abcb.gov.au because we certainly intend to support livable housing
8:59
provisions when they're finalized with detailed education so please watch this space abcb.gov.au.