This video from the 2022 NCC Seminars discusses Section G Ancillary provisions from NCC 2022 Volume One.

Transcript

0:00

[Music]

0:10

Hello my name is Graham Moss, i'm the Principal Building Surveyor  for the Australian Building Codes Board

0:15

this video is a brief update on NCC 2022 ancillary provisions Section G.

0:21

The first change to cover today is G1D4, what's  known in 2019 as G1.3 and that's outdoor play  

0:29

spaces for early childhood centers. Now it's  always been the case that the outdoor play  

0:33

space needs a 1926.1 compliant pool fence that  is 1926.1 the reference standard for pool fencing. 

0:40

So for this reason the fence which is at the  edge of an outdoor play space will need to be  

0:45

at least 1.2 meters tall. This year we've added (1) (b) and (c) as shown by the orange line on this slide  

0:52

for where there is a fall of two meters or more, now  this fall could be because of the retaining wall.

0:57

For instance or for other landscaping, however  this provision was developed to cover outdoor  

1:01

play spaces that are found on balconies  or on rooftop spaces. So if you have a  

1:06

2 meter fall the fence needs to be at least  1.8 meters tall to meet these requirements.

1:13

Next I want to cover is Part G5 construction  in bushfire prone areas there's been some  

1:19

significant changes this year, because  under NCC 2019 in the national provisions  

1:24

the only buildings that Volume One requires  to meet bushfire requirements are a

1:30

Class 2 or 3 building or an associated  Class 10a like a deck or a bin store.

1:36

For NCC 2022 we have a new section  for the Class 9 buildings that you  

1:41

see listed here they're hospitals, early  childhood centers, primary and secondary  

1:45

schools and residential care buildings such  as aged care buildings. Now note this isn't  

1:50

every type of Class 9 building for example  you don't see a sports stadium listed here  

1:55

these particular building types are ones  where the occupants are vulnerable and  

1:59

therefore it's appropriate to provide extra  provisions to protect them in a bushfire event.

2:06

I'll take you to those extra provisions shortly  but the first thing to note if these Deemed-to-Satisfy 

2:11

provisions for these special Class  9 buildings apply only to BAL 12.5  

2:17

now you're probably aware of the AS 3959  bushfire attack level the BAL rating  

2:21

system, that's a risk rating system which based  on the likelihood of exposure to bushfire attack.

2:27

These DtS provisions for certain Class 9 buildings  run out at BAL 12.5, if you go up to  

2:34

BAL 19 or above you need to do a performance solution  however up to bushfire prone land up to BAL 12.5

2:41

are covered by these Deemed-to-Satisfy provisions. If you're familiar with the  

2:45

current bushfire provisions for Class 2 and  3 buildings you'd be aware that for these  

2:49

particular buildings we refer you to AS 3959 for  construction requirements. Now for these special  

2:55

Class 9 buildings it's different we don't refer  to AS 3959 instead we send you to Specification 43  

3:01

which contains the construction requirements for  these special buildings, now these construction  

3:06

requirements do exceed those that are found in  AS 3959 I'll step you through those right now.

3:12

First provision to show you is clause 2 in Specification  43 separation from classified vegetation now this  

3:19

is quite similar to requirements found in  AS 3959 what we're requiring is a minimum  

3:24

distance from vegetation that's specified  and that's a concept straight from AS 3959.

3:30

Next is clause 3 separation between buildings  you have three options and I'll explain those  

3:35

options using the hypothetical scenario with these  three buildings A, B and C the first option is a  

3:42

distance of at least 12 meters between buildings  as is the case between A and B here. If you have  

3:48

12 meters or more then you meet the requirements  but buildings B and C are within 12 meters of each  

3:53

other and that's where clause 2(b) comes in there  are more options inside this Clause that both  

3:59

involve envelope protection so the first option is  to provide frl60/60/60 walls as shown on building B.

4:07

The next option as shown on building C is a tested  envelope system now that entire envelope needs to  

4:15

be submitted to a test under AS 1530.8.1 for a  flux of at least 10 kilowatts per square meter.

4:23

Now AS 1530.8.1 isn't a primary reference in  NCC 2019 however it is caught up by AS 3959  

4:31

it's the standard that's used by manufacturers  and people like that to test windows, doors and  

4:36

other things to find out what BAL those could  withstand and of course it can be used also  

4:40

for to rate a wall or a roof system as an option  for buildings within 12 meters of another building.

4:47

So that's clause 2 separation between  buildings we also require separation from  

4:52

hazards including a boundary or  an open car park that's clause 4.  

4:56

clause 5 requires protection from other  hazards like a bin compound now that  

5:01

needs to be at least 10 meters but if you  don't achieve 10 meters you can use the  

5:05

same protection methods that I outlined before  an frl60/60/60 wall or the tested envelope system.

5:13

So with four provisions about separation you  can see that this is an important part of the  

5:17

fire safety strategy for bushfire protection for  these Class 9 buildings and of course that's not  

5:21

new it's a established way of protecting buildings  from the effects of bushfire. However that's not  

5:27

all we also have clause 6 which is requiring  a non-combustible path at least one and a half  

5:32

meters wide around the building so you can't  have garden beds for instance right up against  

5:36

your building. Next is clause 7 access pathways  what you'll find in this provision are additional  

5:42

requirements beyond those found in D1.10 for exit  pathways from buildings. Clause 9 is important to  

5:49

note there needs to be internal tenability  maintained for the duration of the bushfire  

5:54

and so clause 9 contains special requirements in  order to ensure that that internal tenability is  

6:00

met. Clause 10 building envelope you have to build  the walls and roof to AS 3959 as if your building  

6:07

is in a BAL 19 Zone even though it's only up to  12.5 for which these provisions supply.

6:14

There's also water supply requirements even  if your building doesn't need a fire hydrant  

6:19

you need to at least have a water supply that  could be a pool or a dam you'll find more

6:24

details in clause 11 of Spec 43. There's  also a requirement for emergency power, now  

6:30

this power system needs to be able to run  the internal tenability systems for clause 9

6:35

and other things for a period of at least  six hours. Signage is also required in clause 13  

6:42

there has to be a sign somewhere saying don't  store combustible material near the building.

6:47

And of course, finally vehicular access has to be  provided as for a large isolated building this  

6:52

requirement is to ensure that the fire brigade can  easily access the building and affect operations.

6:58

Now this is a very brief overview of the  new Class 9 bushfire provisions, if you are  

7:02

working with Class 9 buildings in bushfire  prone areas I do recommend that you have a  

7:05

closer look at Part G5 and Specification  43 in the production version of NCC 2022.

7:14

Also new for Section G is livable housing or  you might know of this as accessible housing  

7:19

this is also in Volume Two in Part H8, what is  livable housing? Well I'll explain it this  

7:25

way currently there are no accessibility  requirements in the NCC for the internal  

7:30

parts for Class 2 unit or indeed for a Class 1a  house to be accessible, there's no requirement  

7:35

under NCC 2019 for these internal dwellings to  be accessible but that changes with NCC 2022.

7:42

Both Volume One and Volume Two refer to a new  ABCB reference standard the Livable Housing  

7:47

Design Standard I've talked about making  these dwellings accessible but livable  

7:52

housing isn't so much about making these  accessible but rather making them adaptable.

7:58

This is a diagram from the standard and under the  standard you need to have a toilet on the entrance  

8:02

level of the dwelling that toilet has to be next  to a wall and though the grab rail doesn't have  

8:07

to be installed for the final inspection you do  need to have blocking or sheeting installed so as  

8:11

to be able to receive a handrail in the future. So the handrail doesn't have to be there for  

8:16

the final inspection but the blocking or the  sheeting needs to be there. So of course this  

8:21

is a way amongst others of how the Livable Housing Standard makes a dwelling adaptable.

8:28

There are other requirements listed on this slide  we're talking about step-free entry, circulation  

8:32

requirements as shown by this diagram here, corridor widths of one meter or more  

8:39

minimum doorway widths, also the requirement for  a step-free shower. Now at the time of recording  

8:44

of this video the technical requirements of  the Livable Housing Standard had not been  

8:48

finalized so of course we're not in position  to update you fully during this video, however  

8:54

do watch our website abcb.gov.au because we  certainly intend to support livable housing  

8:59

provisions when they're finalized with detailed  education so please watch this space abcb.gov.au.