Delete clause J4D3 and insert NSW J4D3 as follows:
(1) Where required, insulation must comply with AS/NZS 4859.1 and be installed so that it—
- abuts or overlaps adjoining insulation other than at supporting members such as studs, noggings, joists, furring channels and the like where the insulation must be against the member; and
- forms a continuous barrier with ceilings, walls, bulkheads, floors or the like that inherently contribute to the thermal barrier; and
- does not affect the safe or effective operation of a service or fitting.
(3) Where required, bulk insulation must be installed so that—
- it maintains its position and thickness, other than where it is compressed between cladding and supporting members, water pipes, electrical cabling or the like; and
- in a ceiling, where there is no bulk insulation or reflective insulation in the wall beneath, it overlaps the wall by not less than 50 mm.
(4) Roof, ceiling, wall and floor materials, and associated surfaces are deemed to have the thermal properties listed in Specification 36.
Notes
Where required is deemed to refer to “Where a development consent specifies that insulation is to be provided as part of the development.”.